
REPAIR PROCEDURE 1 (Areas B and D pressure reading in Fig.2C-1)
CONDITION / COMPLAINT POSSIBLE CAUSE ACTION
Discharge Air:- Slightly cool to
warm.
Thermal expansion valve
sweating or has a frost build up
on it.
Low Side Gauge Reading:- Low
(or vacuum)
High Side Gauge Reading :-
Low
Thermal expansion valve remains closed
or blocked.
Thermal expansion valve jammed closed
causing insufficient refrigerant flow to the
suction side of the compressor. This is
normally related to the thermal expansion
valve sensing bulb malfunction or from
being disconnected from the tube, foreign
material in thermal expansion valve or
moisture entry causing rust formations.
Confirm by thorough physical inspection of
all tubes, hoses and components. In
normal operation, the evaporator inlet
temperature is hot. If the inlet pipe is cool,
check for high side restriction. If the inlet
pipe is room temperature, confirm thermal
expansion valve is blocked by running
engine at 2000 RPM - neither high or low
pressure should change by more than 140
kPa.
If the thermal expansion valve proves to be
blocked, replace thermal expansion valve.
Verify repair by repeating the performance
test as detailed in 2.4 AIR CONDITIONING
PERFORMANCE TEST in this Section.
Discharge Air:- Slightly cool to
warm.
High pressure side tubes are
cool and showing signs of
sweating or moisture build up at
a point after a restriction
Low Side Gauge Reading:- Low
High Side Gauge Reading :-
Low
Restriction in high side of system or faulty
compressor control valve.
Foreign material causing blockage
between the compressor outlet and
evaporator inlet (high side).
Very little or no refrigerant flow to suction
(low) side of compressor.
Test compressor control valve by running
engine at 1500 rpm for 10 minutes with air
conditioning controls set to; maximum/full
cold with lowest blower fan speed. Close
doors and windows, open engine hood.
If the low side gauge reads less than
200kPa, replace the compressor control
valve.
If the compressor control valve is okay,
check system for blockages and repair as
necessary.
Verify repair by repeating the performance
test as detailed in 2.4 AIR CONDITIONING
PERFORMANCE TEST in this Section.
Discharge Air:- Slightly cool to
warm.
Low Side Gauge Reading:- Low
High Side Gauge Reading :-
Low
Refrigerant undercharged.
Refrigerant leak from system. Evacuate and leak test the air conditioning
system, refer 2.1 SYSTEM CHARGING
AND EVACUATION in Section 2C AIR
CONDITIONING - SERVICING AND
DIAGNOSIS of this Service Information
CD.
Verify repair by repeating the performance
test as detailed in 2.4 AIR CONDITIONING
PERFORMANCE TEST in this Section.