
EVACUATION AND LEAK TEST
1. Check that both manifold hand valves of the gauge set are closed and turn the RRU off.
2. Connect the charging hoses onto the suction (low) and discharge (high) service valves in the system.
NOTE: DO NOT USE SPANNERS.
3. Connect the centre manifold charging hose to the vacuum pump inlet.
4. Start the vacuum pump and slowly open LOW SIDE manifold hand valve. Low side gauge reading should
decrease to 98 – 102 k Pa vacuum and the high side gauge should read s lightly below the zero index of gauge.
If high side gauge reading does not register, check system for a blockage or leak.
NOTE: When high side gauge is slightly below the zero index of the gauge, open the high side manifold hand valve.
5. After evacuating the system for 15 minutes to a vacuum of –100 kPa, close both the low and high side hand
valves, then stop the vac uum pum p. The system mus t hold a vacuum of –100kPa for a m inim um of 15 minutes .
If the specified vacuum is held then the system has no leaks and may continue to be evacuated for a further
15 minutes.
6. Wear safety goggles.
7. Connect the centre charging hose to the charging cylinder hand valve on the bottom of the cylinder. Open the
bottom charging cylinder hand valve. Do not open the low or high side valves on the manifold gauge at this
time.
8. Loosen the centre charging hose nut connected to the centre fitting of the manifold gauge set until a hiss can be
heard. Allow the air to escape for a few seconds, then re-tighten the nut.
NOTE: DO NOT START ENGINE.
9. Partially charge the system with 200 g of R134a by slowly opening the high side manifold hand valve; low side
gauge should register a pressure, if not, check for blockage. Close the high side manifold hand valve as soon
as 200 g of R134a has entered the system.
10. Check sys tem f or leaks with an electronic detector. If a leak is detected, rem ove refrigerant f rom system using
the RRU and repair the faulty component or connection. Repeat Steps 4 to 10 after repair of leak.
NOTE: Various types and makes of leak detectors are currently in use. Whichever leak detector is used, it is
important to follow the manufacturer’s instructions in regard to adjustment and setting the instrument prior to
conducting the test. Inspect for leaks by slowly moving the probe of the detector around all hose connections and
points of possible leakage. Refrigerant R134a is heavier than air and will be more apparent at the bottom of a fitting.
CHARGING SYSTEM
After a leak check has proven the system to be leak free, charge the proper amount of refrigerant into the system
as follows:
1 Open the HIGH SIDE manifold hand valve slowly. Fill the system with as much of the specified charge as
possible, then close the high side manifold hand valve.
2. Rotate the c ompres s or by hand for 12 revolutions to ens ure no liquid r ef r igerant is tr apped in the suc tion s ide of
the compressor. Failure to comply with this Step may result in damage to the compressor.
3. Start the engine and engage the compressor clutch and evaporator fan on high speed.
4. Set engine speed to 1500 – 1700 rpm.
5. If the system has been charged with the specified amount (775 – 825 g), go to Step 7.
6. To complete the charging of the system, slowly open the LOW side manifold hand valve until the specified
amount has been charged into the system.
CAUTION: Do not allow more than 275 kPa to be registered on the LOW pressure gauge.
7. Perform Cooling System Pressure Test, refer to COOLING SYSTEM PRESSURE TEST in the following
Sections:
Section 6B1 ENGINE COOLING – V6
Section 6B1-2 ENGINE COOLING – V6 SUPERCHARGED
Section 6B3 ENGINE COOLING – GEN III V8
If the unit operates satisfactorily, stop the engine, shut the stop valves at the hose connections to the system
and disconnect the hoses taking extreme caution, as the discharge hose can have up to 2070 kPa stored in it.
Install service valve caps as required.
WARNING: NEVER RUN THE COMPRESSOR WITHOUT REFRIGERANT IN SYSTEM AS COMPRESSOR
LUBRICANT RELIES ON REFRIGERANT FLOW.
No sight glass is fitted to the system due to PAG oil’s foaming properties, which may be confused with a low gas
charge. Topping up of the system is not recommended.