
REPAIR PROCEDURE 1 (AREA S B AND D PRESSURE READING IN FIG. 2C-5)
CONDITION / COMPLAINT POSSIBLE CAUSE ACTION
Discharge Air:- Slightly cool to
warm.
Thermal expansion valve
sweating or has a frost build up
on it.
Low Side Gauge Reading:- Low
(or vacuum)
High Side Gauge Reading :-
Low
Thermal expansion valve remains closed
or blocked.
Thermal expansion valve jammed closed
causing insufficient refrigerant flow to the
suction side of the compressor. This is
normally related to the thermal expansion
valve sensing bulb malfunction or from
being disconnected from the tube, foreign
material in thermal expansion valve or
moisture entry causing rust formations.
Confirm by thorough physical inspection of
all tubes, hoses and components. In
normal operation, the evaporator inlet
temperature is hot. If the inlet pipe is cool,
check for high side restriction. If the inlet
pipe is room temperature, confirm thermal
expansion valve is blocked by running
engine at 2000 RPM - neither high or low
pressure should change by more than 140
kPa.
If the thermal expansion valve proves to be
blocked, replace thermal expansion valve.
Verify repair by repeating the performance
test as detailed in this Section.
Discharge Air:- Slightly cool to
warm.
High pressure side tubes are
cool and showing signs of
sweating or moisture build up at
a point after a restriction
Low Side Gauge Reading:- Low
High Side Gauge Reading :-
Low
Restriction in high side of system or faulty
compressor control valve.
Foreign material causing blockage
between the compressor outlet and
evaporator inlet (high side).
Very little or no refrigerant flow to suction
(low) side of compressor.
Test compressor control valve by running
engine at 1500 rpm for 10 minutes with air
conditioning controls set to; maximum/full
cold with lowest blower fan speed. Close
doors and windows, open engine hood.
If the low side gauge reads less than
200kPa, replace the compressor control
valve.
If the compressor control valve is okay,
check system for blockages and repair as
necessary.
Verify repair by repeating the performance
test as detailed in this Section.
Discharge Air:- Slightly cool to
warm.
Low Side Gauge Reading:- Low
High Side Gauge Reading :-
Low
Refrigerant undercharged.
Refrigerant leak from system. Evacuate and leak test the air conditioning
system, refer 2.2 SYSTEM CHARGING
AND EVACUATION
Verify repair by repeating the performance
test as detailed in this Section.
REPAIR PROCEDURE 2 (AREA C PRESSURE READING IN FIG. 2C-5)
CONDITION / COMPLAINT POSSIBLE CAUSE ACTION
Discharge Air:- Slightly cool to
warm.
Compressor clutch may
continually cycle on the high
pressure switch. Compressor
may also be noisy when
operating.
Low Side Gauge Reading:- Low
to normal
High Side Gauge Reading :-
high to very high
Refrigerant overcharged, restricted filter
drier receiver, blocked or obstructed
condenser fins (airflow), cooling system
overheating, faulty cooling fan operation,
or drive belt slippage.
Referring to the appropriate Sections of
this Service Information CD, check, and
repair as necessary, the following:
• Ensure cooling fans are operating
correctly.
• Check cooling system operation.
• Physically check for blocked or
restricted condenser fins, clean or
remove obstruction.
• Check compressor drive belt for
damage, slippage or incorrect
operation.
• Touch the filter drier receiver inlet and
outlet pipes; if there is a temperature
difference between these two pipes,
replace the filter drier receiver.
If all the above are okay, recharge the air
conditioning system with refrigerant, refer
to 2.2 SYSTEM CHARGING AND
EVACUATION
Verify repair by repeating the performance
test as detailed in this Section.